Relay Protection Coordination for Photovoltaic Power Plant Connected on Distribution Network

التفاصيل البيبلوغرافية
العنوان: Relay Protection Coordination for Photovoltaic Power Plant Connected on Distribution Network
المؤلفون: Nikolovski, Srete, J. J. Strossmayer University of Osijek, Faculty of Electrical Engineering, srete.nikolovski@etfos.hr, Papuga, Vanja, J.J. Strossmayer University of Osijek, Faculty of Electrical Engineering, Knežević, Goran
المصدر: International Journal of Electrical and Computer Engineering Systems; Vol.5. No.1.; ISSN 1847-6996 (Print); ISSN 1847-7003 (Online)
بيانات النشر: Faculty of Electrical Engineering, J.J. Strossmayer University of Osijek
سنة النشر: 2014
المجموعة: Hrčak - Portal of scientific journals of Croatia / Portal znanstvenih časopisa Republike Hrvatske
مصطلحات موضوعية: distribution, inverter, PV power plant, relay protection, short circuit
الوصف: This paper presents a procedure and computation of relay protection coordination for a PV power plant connected to the distribution network. In recent years, the growing concern for environment preservation has caused expansion of photovoltaic PV power plants in distribution networks. Numerical computer simulation is an indispensable tool for studying photovoltaic (PV) systems protection coordination. In this paper, EasyPower computer program is used with the module Power Protector. Time-current relay curves will be computed and plotted for all protection devices in the network and the PV power plant. Protection relay AREVA Micom is placed on the secondary side of a 10 kV feeder and has overcurrent and ground fault protection. The HV side of the transformer station where a PV power plant is connected has an HV fuse. On the secondary side of the transformer there is a low-voltage (LV) circuit breaker Končar 400A with overcurrent, under/over voltage, under/over frequency and ground fault protection. Furthermore, the fuse in the supplying cable for the PV plant is installed as well as the LV breaker in the PV switchboard. Each SMA Tripod inverter is protected with the fuse and the RCD relay. All these relays are modeled and short circuit analysis is performed on several places in the network and the PV power plant and the transformer station. Three phase and single phase to ground faults were considered. Time-current plots were presented and a relay setting is suggested in order to satisfy selectivity and backup protection.
نوع الوثيقة: text
وصف الملف: pdf
اللغة: English
العلاقة: http://hrcak.srce.hr/134407Test; http://hrcak.srce.hr/file/198370Test
الإتاحة: http://hrcak.srce.hr/134407Test
http://hrcak.srce.hr/file/198370Test
حقوق: Copyright Authors of the International Journal of Electrical and Computer Engineering Systems must transfer copyright to the publisher in written form. Subscription Information The annual subscription rate is 50€ for individuals, 25€ for students and 150€ for libraries.
رقم الانضمام: edsbas.1150D99B
قاعدة البيانات: BASE